Installing the XW Automatic Generator Start
975-0307-01-01 2–19
Type 11
Type 11 is a two-wire run mode configuration intended for Kohler
generators. It requires only two wires and one relay to control the
generator. Relay 1 closes momentarily once to start the generator, and
closes momentarily again to stop the generator.
Figure 2-15
Type 11 Connection Diagram
For additional information, see
“Circuit Limitations” on page 2–5.
XW AGS Harness Wires Generator Wires
16
14
13
12
Relay 1
5A fuse
GENERATOR RUN SIGNAL
GENERATOR BATTERY NEGATIVE (–)
RUN
Table 2-14
Type 11 Relay and Timing Preset Configurations
Relay Function Preset Configuration Setting
Relay 1 mode
MomentaryRun
Relay 3 mode
No function
Gen Run signal hold time
0.5 s
Preheat time
0 s
Preheat to crank delay
0 s
Crank time
10 s
Crank retry time
15 s
Gen Cool Down
30 s
Shutdown bypass time
0 s
Start tries
3