Installing the XW Automatic Generator Start
975-0307-01-01 2–9
Type 1
Type 1 is a three-wire GlowStop configuration recommended for “three-
wire” generators with glow plugs that need to be operated before a start is
attempted.
Figure 2-3
Type 1 Connection Diagram
18
17
16
14
13
12
Relay 1
Relay 2
5A fuse
5A fuse
GENERATOR RUN SIGNAL
GENERATOR BATTERY NEGATIVE ()
PREHEAT
START
XW AGS Harness Wires Generator Wires
For additional information, see
“Circuit Limitations” on page 2–5.
Table 2-4
Type 1 Relay and Timing Preset Configurations
Relay Function Preset Configuration Setting
Relay 1 mode
GlowStop
Relay 3 mode
No function
Gen Run signal hold time
0.5 s
Preheat time
20 s
Preheat to crank delay
1 s
Crank time
15 s
Crank retry time
30 s
Gen Cool Down
30 s
Shutdown bypass time
0 s
Start tries
3