Relay Timing
C–2 975-0307-01-01
RunMode
For generators with RunMode starting types (Types 7 and 8):
Relay 1 (RunStop relay) can be used for two-wire configured
generators.
Relay 1 (RunStop) and Relay 2 (Start) can be used with a common
ground for three-wire configured generators.
The Preheat will never overlap the Crank Time.
The “Delay” refers to the “Preheat to Crank Delay” and may be zero.
Cranking will cease when the generator run signal goes high for the
specified hold time or when the crank time has elapsed.
Figure C-1
RunMode Timing Diagram